5.3.3Fire Fighting Appliances

5.3.3.1General .1All fire appliances must be adequate for the expected fire risk. Where appropriate appliances

must comply with Directive 2014/90/EU on Marine Equipment, as amended. .2Multi-purpose fire extinguishers can deal with both category A fires (involving solid materials) and

category B fires (involving liquids or liquefiable solids), and are marked with the multi-purpose rating, e.g., 13A/113B (see paragraphs 5.3.3.2.3, 5.3.3.3.1 and 5.3.3.4.1 below) and 5A/34B (see paragraphs 5.3.3.2.4 and 5.3.3.3.2 below). A wide variety of extinguisher types and sizes are available to meet the fire rating requirements, and advice on suitability should be sought from suppliers.

.3Fire extinguishers must be regularly serviced as recommended by the manufacturers and be fitted

in ready accessible positions, mounted vertically and adequately secured.

.4The use of halons is prohibited, in accordance with Regulation (EC) No 1005/2009 (as amended)

on substances that deplete the ozone layer. New fixed or portable fire extinguishers containing halons must not be used, and existing fixed or portable halon fire extinguishers are to be decommissioned and replaced with halon-free alternatives.The use of CO2 fire extinguishers in accommodation spaces should be avoided.

.5Fire buckets may be of metal, plastic or other suitable material and must be sufficiently robust for

the intended purpose.

.6In a decked vessel, an efficient smoke/fire detection system must be fitted in the machinery space

at the next renewal survey.

5.3.3.2Requirements for decked vessels of 9.0m to less than 15.0m Length overall .1One jet of water to reach any part of the vessel. This is to be demonstrated using a self-priming

hand fire pump fitted above deck level, with the sea suction outside the machinery space. If the self-priming hand pump is also used for bilge pumping duties, a change-over valve must be fitted at the pump position outside the machinery space. One hose with a 10mm spray/jet nozzle must be provided. .2In vessels constructed of wood, a CO2 or water spray fire extinguishing system is to be fitted in the

machinery space.

.3Two portable multi-purpose fire extinguishers with minimum fire rating of 13A/113B, suitable for

extinguishing oil-based machinery space fires.

.4In addition, two portable multi-purpose fire extinguishers with a minimum fire rating of 5A/34B

suitable for extinguishing electrical or accommodation fires.

.5One fire bucket and lanyard.

5.3.3.3Requirements for decked vessels of 6.0m to less than 9.0m Length overall .1Two portable multi-purpose fire extinguishers with a minimum fire rating of 13A/113B, suitable

for extinguishing oil-based machinery room fires. .2In addition, for a vessel fitted with accommodation spaces, one portable multi-purpose fire

extinguisher with a minimum fire rating of 5A/34B, suitable for extinguishing electrical or accommodation fires.

.3One fire bucket and lanyard.

5.3.3.4Requirements for decked vessels of less than 6.0m Length overall .1One portable multi-purpose fire extinguisher with a minimum fire rating of 13A/113B, suitable for

extinguishing oil-based machinery room fires. .2One fire bucket and lanyard.

5.3.3.5Requirements for open boats .1One portable multi-purpose fire extinguisher with a minimum fire rating of 13A/113B. When an

inboard/outboard engine is fitted, the extinguisher must be suitable for extinguishing oil/petrolbased fires. .2One fire bucket and lanyard.

5.3.3.6Requirements for all vessels .1Means of closing all skylights, doorways, vents and funnel openings to machinery spaces and

remote controls, operable from outside the machinery space, to fuel tank outlet valves shall be provided.